System Specifications:
Product Water Produced per hour of operation:
+-15% 850 psi / 56 Bar, 77oF / 25oC & 35,000 ppm TDS typical sea water
Model |
Production Per Hour |
Production Per 24 Hours |
gallons / liters |
gallons / liters |
|
42m3/S2 |
458 / 1,735 |
11,000 / 41,639 |
76m3/S2 |
833 / 3,155 |
20,000 / 75,708 |
98m3/S2 |
1,083 / 4,101 |
26,000 / 98,420 |
121m3/D2 |
1,333 / 5,047 |
32,000 / 121,133 |
132m3/D2 |
1,458 / 5,520 |
35,000 / 132,489 |
144m3/D2 |
1,583 / 5,994 |
38,000 / 143,845 |
144m3/D3 |
1,583 / 5,994 |
38,000 / 143,845 |
159m3/D3 |
1,750 / 6,624 |
42,000 / 158,987 |
167m3/D3 |
1,833 / 6,940 |
44,000 / 166,558 |
Salt Rejection (Chloride Ion):
Minimum 99.2%, Average 99.4%
Product Water Temperature:
Ambient to feed water temperature.
Salinity Monitoring:
Automatic electronic monitoring. Temperature compensated with solid state "DOT LED" continuous readout in micromhos per cm3 and of a fail safe design.
Salinity Range:
Sea Water Systems (SW suffix) up to 35,000 ppm TDS (Nacl)
High Rejection Systems (HR suffix) up to 50,000 ppm TDS (Nacl)
Temperature Range:
Min. 33oF / .5oC Max. 122oF / 50oC
Reverse Osmosis Membrane:
High Rejection/High Yield aromatic tri-polyamind, thin film composite, spiral wound, single pass reverse osmosis membrane element. SW suffix use Sea Water Elements, and HR suffix use High Rejection Elements.
Chlorine Tolerance:
0.1 ppm
pH Range:
3-11 (typical seawater pH is 8)
System Pressure:
| System Feed Water Inlet: | 1-1/2" Flange |
| System Rinse/Cleaning Chemical Inlet: | 1-1/2" Flange |
| Brine Discharge: | 1-1/2" Flange |
| Rinse/Cleaning Chemical Return: | 1-1/2" Flange |
| Product: | 1" Flange |
System Operation
Typical seawater has a salinity of 35,000 ppm TDS and an average temperature of 77oF / 25oC. Nominal: 850 psi / 59 bar / 59.7 Kg/cm2. (Brackish varies w/ppm)
Weight:
Model Number |
Weight |
42m3/S2 |
3700 lbs / 1678 Kg |
76m3/S2 |
4000 lbs / 1814 Kg |
98m3/S2 |
4300 lbs / 1950 Kg |
121m3/D2 |
4800 lbs / 2177 Kg |
132m3/D2 |
5100 lbs / 2313 Kg |
144m3/D2 |
5400 lbs / 2449 Kg |
144m3/D3 |
5400 lbs / 2449 Kg |
159m3/D3 |
5850 lbs / 2653 Kg |
167m3/D3 |
6300 lbs / 2857 Kg |
External Installation Water Connections:
Pipe sizes to be supplied by the installer for connection of the Horizon Reverse Osmosis supplied components.
| Inlet: | 1-1/2" Flange |
| Brine: | 1-1/2" Flange |
| Product: | 1" Flange |
High Pressure Pump Electric Motor:
(HP = Horse Power; FLA = Full Load Amperes, LRA = Locked Rotor Amperes @ StartUp)
High Pressure Pump Electric Motor Three Phase:
Hz |
VAC |
HP |
FLA |
LRA |
Motor |
50 |
220 |
50 |
120 |
792 |
SRM4110T-50 |
50 |
380 |
50 |
70 |
458 |
SRM4110T-50 |
50 |
440 |
50 |
60 |
396 |
SRM4110T-50 |
60 |
200 |
50 |
120 |
648 |
SRM4110T-8 |
60 |
208 |
50 |
120 |
877 |
SRM4311 |
60 |
230 |
50 |
120 |
618 |
SRM4115T |
60 |
460 |
50 |
60 |
309 |
SRM4115T |
Booster Pump Electric Motor Three Phase:
Hz |
VAC |
HP |
FLA |
LRA |
50 |
220 |
3 |
8 |
64 |
50 |
380 |
3 |
4 |
32 |
50 |
440 |
3 |
4 |
30 |
60 |
208 |
3 |
9 |
64 |
60 |
230 |
3 |
8 |
58 |
60 |
460 |
3 |
4 |
29 |
Feed Water Pump Electric Motor Three Phase:
Hz |
VAC |
HP |
FLA |
LRA |
50 |
220 |
5 |
13 |
108 |
50 |
380 |
5 |
7 |
54 |
50 |
440 |
5 |
7 |
52 |
60 |
208 |
5 |
14 |
110 |
60 |
230 |
5 |
13 |
100 |
60 |
460 |
5 |
7 |
50 |
Recommended Circuit Breaker:
The actual final system configuration may have an optional Feed Water Pump and/or different size Booster Pump therefore size your Circuit Breaker accordingly. The below chart is an approximation assuming 3 horse power High Pressure Pump and 3 horse power Booster Pump.
Operating Voltage Hz & Phase |
Rec. Circuit Breaker Size 3
HP Feed Water & Booster Pumps |
| 50 HP HPP Motor | |
220 VAC, 50 Hz, Three Phase |
150 Amperes |
380 VAC, 50 Hz, Three Phase |
90 Amperes |
440 VAC, 50 Hz, Three Phase |
75 Amperes |
200 VAC, 60 Hz, Three Phase |
160 Amperes |
208 VAC, 60 Hz, Three Phase |
160 Amperes |
230 VAC, 60 Hz, Three Phase |
150 Amperes |
460 VAC, 60 Hz, Three Phase |
75 Amperes |